5-30

Using the I/O

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

With any drive, you can use the controller data table addresses to directly
control and monitor the drive without creating any ladder logic program.
However, if you intend to use Human Machine Interface devices
(PanelView, and so forth) to operate the drive and view its status, you will
need to create descriptive controller data table addresses (

Table 5.M

and

Table 5.N

) and a ladder logic program that will pass that data to the data

table addresses used for messaging.

Table 5.M PLC-5 and Program Data Table Address Descriptions for Example Logic

Status/Feedback Ladder Logic Program

Table 5.N Program and PLC-5 Data Table Address Descriptions for Example Logic

Command/Reference Ladder Logic Program

An example ladder logic program that uses these descriptive controller data
table addresses and passes their data to the descriptive program data table
addresses is shown in

Figure 5.16

and

Figure 5.17

.

Description

PLC-5 Data

Table Address

Description

Program Data

Table Address

Drive Ready

N9:1/0

Status Ready

B3:1/0

Drive Active

N9:1/1

Status Active

B3:1/1

Actual Direction (XIO)

N9:1/3

Status Forward

B3:1/3

Actual Direction (XIC)

N9:1/3

Status Reverse

B3:1/4

Drive Faulted

N9:1/7

Status Faulted

B3:1/7

Drive At Speed

N9:1/8

Status At Speed

B3:1/8

Speed Feedback

N9:2

Speed Feedback

N20:2

Description

Program Data

Table Address

Description

PLC-5 Data

Table Address

Command Stop

B3:20/0

Drive Stop

N10:1/0

Command Start

B3:20/1

Drive Start

N10:1/1

Command Jog

B3:20/2

Drive Jog

N10:1/2

Command Clear Faults

B3:20/3

Drive Clear Faults

N10:1/3

Command Forward Reverse (XIO) B3:20/4

Drive Forward

N10:1/4

Command Forward Reverse (XIC) B3:20/4

Drive Reverse

N10:1/5

Speed Reference

N30:2

Speed Reference

N10:2