6-42

Using Explicit Messaging

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

Table 6.U Example Scattered Read COP Response Data

Figure 6.47 Example Scattered Read COP Response Data File

SLC 500 Controller Example COP Message to Write Multiple Parameters

A scattered write message is used to write values to multiple parameters.
Values for up to 8 parameters can be written. This write message example
writes the following values to these five parameters.

Address

Value

Description

Hex.

(1)

(1)

In RSLogix 5 software, leading zeros are not displayed in data file addresses. For example, ‘001E’ in address

N30:71 is shown as ‘1E’.

Dec.

N30:70

0101

257

TXID = 01, Status = 01 (successful)

N30:71

001E

30

Port = 00, Size = 30 bytes

N30:72

CB01

51969

Service = CB (successful), Address = 01 (Node)

N30:73

0001

1

Read Value = Parameter Number (verification)

N30:74

0384

(2)

(2)

For PowerFlex 700S or PowerFlex 750-Series drives, if some of the parameters being read are floating point

(REAL) data types, see the ‘Communications’ section in Chapter 1 of the PowerFlex 700S AC Drives Phase II

Control Reference Manual, publication PFLEX-RM003, on how to manipulate REAL data into a proper Float tag.

900

Parameter Value (LSW) = 90.0 Hz.

N30:75

0000

(2)

0

Parameter Value (MSW) = 0

N30:76

0003

3

Read Value = Parameter Number (verification)

N30:77

0009

(2)

9

Parameter Value (LSW) = 0.09 Amp

N30:78

0000

(2)

0

Parameter Value (MSW) = 0

N30:79

0006

6

Read Value = Parameter Number (verification)

N30:80

08EE

(2)

2286

Parameter Value (LSW) = 228.6 VDC

N30:81

0000

(2)

0

Parameter Value (MSW) = 0

N30:82

000C

12

Read Value = Parameter Number (verification)

N30:83

0CA7

(2)

3239

Parameter Value (LSW) = 323.9 VDC

N30:84

0000

(2)

0

Parameter Value (MSW) = 0

N30:85

0011

17

Read Value = Parameter Number (verification)

N30:86

207E

(2)

8318

Parameter Value (LSW) = 8.318 mA

N30:87

0000

(2)

0

Parameter Value (MSW) = 0

PowerFlex 7-Class Drive Parameter

Write Value

141 - [Accel Time 2]

11.1 Sec.

143 - [Decel Time 2]

22.2 Sec.

105 - [Preset Speed 5]

33.3 Hz.

106 - [Preset Speed 6]

44.4 Hz.

107 - [Preset Speed 7]

55.5 Hz.