Table 5.F PLC-5 or SLC 500 Controller I/O Image for Drives with 32-bit Reference/

Feedback and 32-bit Datalinks

These products include the following:

Using Logic Command/

Status

The Logic Command is a 16-bit word of control data produced by the
controller and consumed by the adapter. The Logic Status is a 16-bit word
of status data produced by the adapter and consumed by the controller.
PowerFlex 750-Series drives have a 32-bit Logic Command/Status—but
when using a 20-COMM-D adapter only the first 16 bits can be used.

This manual contains the bit definitions for most compatible products
available at the time of publication in

Appendix D

,

Logic Command/Status

Words

. For other products, see their documentation.

Using Reference/Feedback

The Reference is produced by the controller and consumed by the adapter.
The Feedback is produced by the adapter and consumed by the controller.
The size of the Reference/Feedback is determined by the drive and can be
displayed with adapter Parameter 07 - [Ref/Fdbk Size].

When the Reference and Feedback are enabled, and a ControlLogix
controller is used, specific controller tags are automatically created, sized

• PowerFlex 700S drives with Phase I or Phase II control

• PowerFlex 753 drives

• PowerFlex 700L drives with 700S control

• PowerFlex 755 drives

Word

Output I/O

Word

Input I/O

0

Logic Command

0

Logic Status

1

Not Used

1

Not Used

2

Reference (LSW)

2

Feedback (LSW)

3

Reference (MSW)

3

Feedback (MSW)

4

Datalink In A1 (LSW)

4

Datalink Out A1 (LSW)

5

Datalink In A1 (MSW)

5

Datalink Out A1 (MSW)

6

Datalink In A2 (LSW)

6

Datalink Out A2 (LSW)

7

Datalink In A2 (MSW)

7

Datalink Out A2 (MSW)

8

Datalink In B1 (LSW)

8

Datalink Out B1 (LSW)

9

Datalink In B1 (MSW)

9

Datalink Out B1 (MSW)

10

Datalink In B2 (LSW)

10

Datalink Out B2 (LSW)

11

Datalink In B2 (MSW)

11

Datalink Out B2 (MSW)

12

Datalink In C1 (LSW)

12

Datalink Out C1 (LSW)

13

Datalink In C1 (MSW)

13

Datalink Out C1 (MSW)

14

Datalink In C2 (LSW)

14

Datalink Out C2 (LSW)

15

Datalink In C2 (MSW)

15

Datalink Out C2 (MSW)

16

Datalink In D1 (LSW)

16

Datalink Out D1 (LSW)

17

Datalink In D1 (MSW)

17

Datalink Out D1 (MSW)

18

Datalink In D2 (LSW)

18

Datalink Out D2 (LSW)

19

Datalink In D2 (MSW)

19

Datalink Out D2 (MSW)

Size

Valid Values

16-bit

-32768…32767

32-bit

-2147483648…2147483647