6-14

Using Explicit Messaging

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

ControlLogix Controller – Formatting a Message to Read Multiple Parameters Using
RSLogix 5000 Software, Any Version

Figure 6.13 Scattered Read Message Configuration Screens

The following table identifies the data that is required in each box to
configure a message to read multiple parameters.

Configuration Tab

Example Value

Description

Message Type

Service Type

(1)

Service Code

(1)

Class

Instance

Attribute

Source Element

Source Length

Destination

CIP Generic

Custom

4b (Hex.)

93 (Hex.)

0 (Dec.)

0 (Hex.)

Scattered_Read_Request_

Internal _Use_Only[0]

(3)

31

(3)

Scattered_Read_Response[0]

Used to access Parameter Object in the adapter.

Required for scattered messages.

Code for the requested service.

Class ID for the DPI Parameter Object.

Required for scattered messages.

Required for scattered messages.

Name of the tag for any service data to be sent from

scanner or bridge to the adapter/drive.

Number of bytes of service data to be sent in the message.

The tag where the data that is read is stored.

Communication Tab

Example Value

Description

Path

(2)

My_DeviceNet_Bridge

The path is the route that the message will follow.

Tag Tab

Example Value

Description

Name

Scattered_Read_Message

The name for the message.

(1)

The default setting for Service Type is ‘Custom’, enabling entry of a Service Code not available from the Service Type pull-down

menu. When choosing a Service Type other than ‘Custom’ from the pull-down menu, an appropriate Hex. value is automatically

assigned to the Service Code box which is dimmed (unavailable).

(2)

Click

Browse to find the path, or type in the name of the device listed in the I/O Configuration folder (for this example,

My_DeviceNet_Bridge). Then always type in ‘2’ which is the DeviceNet scanner port, followed by a comma, and then the node of the

drive (for this example, ‘1’).

(3)

In this example, we are reading five parameters. Each parameter being read requires an array of three INT registers. Therefore, a

controller tag was created with its Data Type field set to ‘INT[15]’. Also, the Source Length field on the Message Configuration screen

must correspond to the selected Data Type in bytes (for this example, 31 bytes total; 30 bytes for an INT[15] array plus one extra

required byte that is always set to zero). Scattered read messages always assume that every parameter being read is a 32-bit integer,

regardless of its actual data type. Maximum length is 133 bytes; 132 bytes or 66 words which equates to 22 parameters plus one

extra required byte.