Setting the data rate switch, Setting the data rate switch -3 – Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual

Page 21

Advertising
background image

Installing the Adapter

2-3

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

Setting the Data Rate Switch

Set the adapter Data Rate switch (

Figure 2.2

) by rotating the switch to the

desired setting.

Figure 2.2 Setting Adapter Data Rate Switch

The Data Rate switch setting can be verified by viewing Parameter 06 -
[DN Rate Act]
or Diagnostic Device Item number 29 (

page 7-5

) with any

of the following drive configuration tools:

• PowerFlex HIM

• Connected Components Workbench software, version 1.02 or later

• DriveExplorer software, version 2.01 or later

• DriveExecutive software, version 3.01 or later

Setting

Description

Auto

Sets the adapter to the data rate used by other network devices. Another

device on the network must be set to a data rate.

125K, 250K, 500K

Sets the adapter to the respective data rate.

PGM (default)

The adapter uses the value stored in

Parameter 05 - [DN Rate Cfg] for the

data rate. See

Setting the Data Rate on page 3-3

. Also, the adapter uses the

value stored in

Parameter 03 - [DN Addr Cfg] for the node address. See

Setting the Node Address on page 3-3

.

125K

250K

500K

PGM

AUTO

Advertising