Setting the data rate switch, Setting the data rate switch -3 – Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual
Page 21

Installing the Adapter
2-3
20-COMM-D DeviceNet Adapter User Manual
Publication 20COMM-UM002G-EN-P
Setting the Data Rate Switch
Set the adapter Data Rate switch (
Figure 2.2
) by rotating the switch to the
desired setting.
Figure 2.2 Setting Adapter Data Rate Switch
The Data Rate switch setting can be verified by viewing Parameter 06 -
[DN Rate Act] or Diagnostic Device Item number 29 (
) with any
of the following drive configuration tools:
• PowerFlex HIM
• Connected Components Workbench software, version 1.02 or later
• DriveExplorer software, version 2.01 or later
• DriveExecutive software, version 3.01 or later
Setting
Description
Auto
Sets the adapter to the data rate used by other network devices. Another
device on the network must be set to a data rate.
125K, 250K, 500K
Sets the adapter to the respective data rate.
PGM (default)
The adapter uses the value stored in
Parameter 05 - [DN Rate Cfg] for the
data rate. See
Setting the Data Rate on page 3-3
. Also, the adapter uses the
value stored in
Parameter 03 - [DN Addr Cfg] for the node address. See
Setting the Node Address on page 3-3
.
125K
250K
500K
PGM
AUTO