Port status indicator, Mod status indicator, Port status indicator -2 mod status indicator -2 – Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual

Page 174

Advertising
background image

7-2

Troubleshooting

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

PORT Status Indicator

This red/green bicolor LED indicates the status of the adapter’s connection
to the drive as shown in the table below.

MOD Status Indicator

This red/green bicolor LED indicates the status of the adapter as shown in
the table below.

Status

Cause

Corrective Action

Off

The adapter is not powered or is not properly

connected to the drive.

• Securely connect the adapter to the drive using the Internal Interface

(ribbon) cable.

• Apply power to the drive (or adapter if mounted in a DPI External

Comms Kit).

Flashing Red

The adapter is not receiving a ping message

from the drive.

• Verify that cables are securely connected and not damaged. Replace

cables if necessary.

• Cycle power to the drive (or adapter if mounted in a DPI External

Comms Kit).

Steady Red

The drive has refused an I/O connection from the

adapter.

Another DPI peripheral is using the same DPI

port as the adapter.

Important: Cycle power to the drive (or adapter if mounted in a DPI

External Comms Kit) after making any of the following corrections:

• Verify that all DPI cables on the drive are securely connected and not

damaged. Replace cables if necessary.

• Verify that the DPI drive supports Datalinks.
• Configure the adapter to use a Datalink that is not already being used

by another peripheral.

Steady Orange

The adapter is connected to a product that does

not support Allen-Bradley DPI communications.

Connect the adapter to a product that supports Allen-Bradley DPI

communications (for example, a PowerFlex 7-Class drive).

Flashing Green

The adapter is establishing an I/O connection to

the drive.

No action required. Normal behavior if no DPI I/O is enabled.

Steady Green

The adapter is properly connected and is

communicating with the drive.

No action required.

Status

Cause

Corrective Action

Off

The adapter is not powered or is not properly

connected to the drive.

• Securely connect the adapter to the drive using the Internal Interface

(ribbon) cable.

• Apply power to the drive (or adapter if mounted in a DPI External

Comms Kit).

Flashing Red

The adapter has failed the firmware test.

The adapter firmware is being updated.

The node address switch setting is not valid.

• Clear faults in the adapter.
• Cycle power to the drive (or adapter if mounted in a DPI External

Comms Kit).

• If cycling power does not correct the problem, the adapter parameter

settings may have been corrupted. Reset defaults and reconfigure the

adapter.

• If resetting defaults does not correct the problem, update the adapter

with the latest firmware revision.

• Verify that the node address switch setting is valid (0…63).

Steady Red

The adapter has failed the hardware test.

• Cycle power to the drive (or adapter if mounted in a DPI External

Comms Kit).

• Replace the adapter.

Flashing Green

The adapter is operational, but is not transferring

I/O data to a controller.

• Place the scanner in RUN mode.

• Program the controller to recognize and transmit I/O to the adapter.

• Configure the adapter for the program in the controller.

• Normal behavior if no DPI I/O is enabled.

Steady Green

The adapter is operational and transferring I/O

data to a controller.

No action required.