Chapter 5, Using the i/o, About i/o messaging – Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual

Page 85: About i/o messaging -1, 5using the i/o

Advertising
background image

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

Chapter

5

Using the I/O

This chapter provides information and examples that explain how to
control, configure, and monitor a PowerFlex 7-Class drive using the
configured I/O.

About I/O Messaging

On CIP-based networks, including DeviceNet, I/O connections are used to
transfer the data which controls the PowerFlex drive and sets its Reference.
I/O can also be used to transfer data to and from Datalinks in PowerFlex
7-Class drives.

The adapter provides many options for configuring and using I/O, including
the following:

• Configuring the size of I/O by enabling or disabling the Logic

Command/Reference and Datalinks

• Setting a Master-Slave hierarchy or a Peer-to-Peer hierarchy

• Using a Change of State, Cyclic, or Polled data exchange method

Chapter 3

,

Configuring the Adapter

, and

Chapter 4

,

Configuring the I/O

,

discuss how to configure the adapter and controller on the network for these
options. The defines the different options. This chapter discusses how to
use I/O after you have configured the adapter and controller.

Topic

Page

About I/O Messaging

5-1

Understanding the I/O Image

5-2

Using Logic Command/Status

5-6

Using Reference/Feedback

5-6

Using Datalinks

5-9

Example Ladder Logic Program Information

5-11

ControlLogix Controller Example

5-12

PLC-5 Controller Example

5-19

SLC 500 Controller Example

5-32

!

ATTENTION: Risk of injury or equipment damage exists. The
examples in this publication are intended solely for purposes of
example. There are many variables and requirements with any
application. Rockwell Automation does not assume responsibility
or liability (to include intellectual property liability) for actual
use of the examples shown in this publication.