Setting the node address, Setting the data rate, Setting the node – Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual

Page 31

Advertising
background image

Configuring the Adapter

3-3

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

Setting the Node Address

If the adapter Data Rate switch (

Figure 2.2

) is set to ‘PGM’ (Program), the

value of Parameter 03 - [DN Addr Cfg] determines the node address. We
recommend not to use the default node address 63 because all new devices
on the network use this address as the default address. Also, node address
63 is used for Automatic Device Recovery (ADR).

1. Set the value of Parameter 03 - [DN Addr Cfg] to a unique node

address.

2. Reset the adapter (see

Resetting the Adapter on page 3-12

).

When the node address is correctly configured and the adapter is connected
to an operational network, the NET A status indicator should be steady
green or flashing green.

Setting the Data Rate

If the adapter Data Rate switch (

Figure 2.2

) is set to ‘PGM’ (Program), the

value of Parameter 05 - [DN Rate Cfg] determines the data rate. The
default Autobaud setting will detect the data rate used on the network if
another device is setting the data rate. Your application may require a
different setting.

1. Set the value of Parameter 05 - [DN Rate Cfg] to the data rate at

which your network is operating.

2. Reset the adapter (see

Resetting the Adapter on page 3-12

).

Port 5 Device
20-COMM-D
Parameter #: 03

DN Addr Cfg

63

0 <> 63

Default = 63

Value

Data Rate

0

125 kbps

1

250 kbps

2

500 kbps

3

Autobaud (default)

Port 5 Device
20-COMM-D
Parameter #: 05

DN Rate Cfg

3

Autodetect