Configuring the I/O

4-29

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

Table 4.G Drives with 32-bit Reference/Feedback and 32-bit Datalinks

These products include the following:

g. Set the scan rate for the selected data exchange method.

For more information about scan rates, see RSNetWorx for
DeviceNet online help.

h. Click OK.

If a Scanner Configuration Applet appears, click Yes to continue.
The Edit I/O Parameters screen closes and then the 1771-SDN
Scanlist tab screen reappears.

12. Click the Input tab to display the input registers for the 1771-SDN

scanner.

Important: If your RSLogix 5 project requires a different memory

selection than the default setting for the drive input image,
set the Memory field to the appropriate setting. For this
example, the default setting of Block Xfer 62 and its
corresponding N-files are used.

• PowerFlex 700S drives with Phase I or Phase II control

• PowerFlex 753 drives

• PowerFlex 700L drives with 700S control

• PowerFlex 755 drives

Logic

Command/

Status

Ref/Fdbk

(32-bit)

Datalinks (32-bit) User Configured Settings

A

B

C

D

Size in Bytes

Par. 13 -

[DPI I/O Cfg]

Par. 25 -

[M-S Input]

Par. 26 -

[M-S Output]

Input Output

8

8

…0 0001

…0 0001

…0 0001

16

16

…0 0011

…0 0011

…0 0011

24

24

…0 0111

…0 0111

…0 0111

32

32

…0 1111

…0 1111

…0 1111

40

40

…1 1111

…1 1111

…1 1111

Data Exchange Method

Rate Field to Set

Polled

Poll Rate

Change of State

Heartbeat Rate

Cyclic

Send Rate