Troubleshooting

7-3

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

NET A Status Indicator

This red/green bicolor LED indicates the status of the network connection
as shown in the table below.

Status

Cause

Corrective Actions

Off

The adapter or network is not powered, or the

adapter is not properly connected to the network.

• Securely connect the adapter to the drive using the Internal Interface

(ribbon) cable and to the network using a DeviceNet cable.

• Correctly connect the DeviceNet cable to the DeviceNet linear plug

(shipped with the adapter).

• Apply power to the drive (or adapter if mounted in a DPI External

Comms Kit) and network.

Steady Red

The adapter failed the duplicate node address

detection test or a bus off condition exists.

• Configure the adapter to use a unique node address on the DeviceNet

network.

• Configure the adapter to use the correct network data rate.
• Verify that the network has the correct media installed.

Flashing Red

An DeviceNet connection has timed out.

• Place the scanner in RUN mode, or apply power to the peer device

that will send I/O.

• Check the amount of traffic on the network.

Flashing

Red/Green

The adapter has received an Identity Comm

Fault request.

Wait for the faulted node recovery to complete.

Flashing Green

The adapter is properly connected but is not

communicating with any devices on the network.

• Place the controller in RUN mode, or apply power to the peer device

that will send I/O.

• Program the controller or peer device to recognize and transmit I/O or

make a messaging connection to the adapter.

• Configure the adapter for the program in the controller or the I/O from

the peer device.

Steady Green

The adapter is properly connected and

communicating on the network.

No action required.