Configuring the I/O

4-13

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

g. Set the scan rate for the selected data exchange method.

For more information about scan rates, see RSNetWorx for
DeviceNet online help.

h. Click OK.

If a Scanner Configuration Applet appears, click Yes to continue.
The Edit I/O Parameters screen closes and then the 1756-DNB
Scanlist tab screen reappears.

12. Click the Input tab to display the input registers for the 1756-DNB

scanner.

13. Click AutoMap to map the drive input image to the 1756-DNB scanner

as shown in this example below.

14. Click the Output tab to display the output registers for the 1756-DNB

scanner.

Data Exchange Method

Rate Field to Set

Polled

Poll Rate

Change of State

Heartbeat Rate

Cyclic

Send Rate

TIP: If your RSLogix 5000 project requires a different starting DWord
(double word, 32-bit) than the default value of 0 for the drive input
image, set the Start DWord field to the appropriate value.