Slc 500 controller example, Configuring parameters for network i/o, Slc 500 controller example -31 – Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual

Page 73

Advertising
background image

Configuring the I/O

4-31

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

16. Click OK.

If the Scanner Configuration Applet appears and asks to download these
settings to the 1771-SDN scanner, click Yes.

17. Click File > Save.

If this is the first time you saved the project, the Save As dialog box
appears.

a. Navigate to a folder.

b. Type a file name.
c. Click Save to save the configuration as a file on your computer.

SLC 500 Controller Example

After the adapter is configured, the connected drive and adapter will be a
single node on the network. This section provides the steps needed to
configure a simple DeviceNet network (see

Figure 4.3

). In our example, we

will configure a SLC 500 controller with 1747-SDN scanner to communicate
with a drive using Logic Command/Status, Reference/Feedback, and
Datalinks over the network.

Figure 4.3 SLC 500 Controller Example DeviceNet Network

Configuring Parameters for Network I/O

Because the I/O for the drive is defined in the next subsection

Use

RSNetWorx for DeviceNet to Configure and Save the I/O to the
Controller on page 4-32

, there is no need to configure any I/O inside the

RSLogix 500 project, version 7.20 or later, until using the I/O as described
in

Chapter 5

.

However, to get the adapter to operate with the I/O created in

Chapter 5

, you

need to configure the adapter to accept the I/O and the drive to point to the
appropriate Datalinks.

Node 0

SLC 5/05 Controller

with 1747-SDN

Node 1

PowerFlex 70 Drive with

20-COMM-D Adapter

Node 62

Computer with

DeviceNet Connection