Configuring the I/O
4-41
20-COMM-D DeviceNet Adapter User Manual
Publication 20COMM-UM002G-EN-P
example, change the default setting of Discrete to M File
and its corresponding M-files are used.
15. Click AutoMap to map the drive output image to the 1747-SDN
scanner as shown in this example below.
16. Click OK.
If the Scanner Configuration Applet appears asking to download these
settings to the 1747-SDN scanner, click Yes.
17. Click File > Save.
If this is the first time you saved the project, the Save As dialog box
appears.
a. Navigate to a folder.
b. Type a file name.
c. Click Save to save the configuration as a file on your computer.
TIP: If your RSLogix 500 project requires a different starting Word
(word, 32-bit) than the default value of 0 for the drive output image, set
the Start Word field to the appropriate value.