Configuring the I/O

4-41

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

example, change the default setting of Discrete to M File
and its corresponding M-files are used.

15. Click AutoMap to map the drive output image to the 1747-SDN

scanner as shown in this example below.

16. Click OK.

If the Scanner Configuration Applet appears asking to download these
settings to the 1747-SDN scanner, click Yes.

17. Click File > Save.

If this is the first time you saved the project, the Save As dialog box
appears.

a. Navigate to a folder.
b. Type a file name.

c. Click Save to save the configuration as a file on your computer.

TIP: If your RSLogix 500 project requires a different starting Word
(word, 32-bit) than the default value of 0 for the drive output image, set
the Start Word field to the appropriate value.