Installing Your Hardware Components 107

4. Connect the ground screw of the power supply to the nearest

ground or ground bus. Use a #14 AWG 75 Deg. Copper wire
(Category 1 per Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1) and keep the leads as short as
possible. The 1746-P4 is shown below.

5. Remove the warning label from the top of the power supply.

6. Connect line power to the power supply.

For the 1746-P1, 1746-P2, 1746-P4, 1746-P5, and 1746-P6 power
supplies, use PWR OUT +24V dc and PWR OUT COM terminals to

IMPORTANT

Terminal screws on the 1746-P1, 1746-P2, 1746-P3, 1746-P5,

1746-P6, and 1746-P7 power supply should be tightened with a

maximum torque of 1 Nm (8.8 lb-in).
Terminal screws on the 1746-P4 power supply should be

tightened with a max torque of 0.8 Nm (7 lb-in).

ATTENTION

If you have a 1746-P3 power supply, see page 64 for special

grounding considerations.

ATTENTION

Your SLC 500 power supply can be damaged by voltage surges

when switching inductive loads such as motors, motor starters,

solenoids, and relays. To avoid damage to your SLC 500 power

supply in these applications, use an isolation transformer to

isolate the power supply from harmful voltage surges.

Chassis Ground

Nearest Ground Bus

Tighten terminal
screws to 0.8 Nm
(7 lb-in)