Publication 1747-UM011G-EN-P - June 2008

Troubleshooting 161

Returning the SLC 5/03, SLC 5/04, and SLC 5/05 Processors to
Initial Factory Conditions

We only recommend this procedure if the communication channels
have been shut down due to the configuration parameters, or if you
absolutely cannot establish communication with the processor.

Follow this procedure to return the processor to initial factory
conditions.

1. Remove power from the SLC 500 power supply.

2. Remove the processor from the chassis.

3. Disconnect the battery by removing the battery connector from

its socket.

4. Locate the VBB and GND connections on the right side of the

motherboard.

5. Place a small bladed screwdriver across the VBB and GND

connections and hold for 60 seconds. This returns the processor
to the initial factory conditions.

WARNING

If you return the processor to the initial factory conditions, the

user program is lost and communication configurations are

returned to their default settings.