Publication 1747-UM011G-EN-P - June 2008

System Installation Recommendations 71

SLC 500 Operation with 24V dc User Power Overcurrent Condition

Power Supply Cat. No.

SLC Operation

Recovery Procedure

1746-P1 series A (made in Japan)

power supply shutdown, CPU fault

Reload user program

1746-P1 series A (made in Malaysia -

current production)

24V dc user shutdown, CPU continues

Correct overcurrent condition

1746-P2 series A and B

power supply shutdown, CPU fault

Reload user program

1746-P2 series C

24V dc user shutdown, CPU continues

Correct overcurrent condition

1746-P4 series A

power supply shutdown, CPU fault

Reload user program

1746-P5 series A

24V dc user shutdown, CPU continues

Correct overcurrent condition

1746-P6 series A

24V dc user shutdown, CPU continues

Correct overcurrent condition

ATTENTION

For 1746-P1 (made in Malaysia), 1746-P2 series C, 1746-P5

series A, and 1746-P6 series A power supply, to avoid

unexpected operation due to 24V dc user power shutdown,

monitor the 24V dc user output with a 24V dc input channel.