A - specifications, Slc 500 system general specifications, Appendix a – Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual

Page 175: Specifications, Appendix

Advertising
background image

175

Publication 1747-UM011G-EN-P - June 2008

Appendix

A

Specifications

This appendix provides the specifications for the SLC 500 processors as well
as the SLC power supplies.

SLC 500 System General
Specifications

The table below lists SLC 500 system test specifications.

Attribute

Value

Industry Standard

Temperature, operating

0 °C...60 °C (32 °F...140 °F)

Not applicable

Temperature, storage

-40 °C...85°C (-40 °F...185 °F)

Not applicable

Humidity

5 to 95% without condensation

Not applicable

Vibration, operating

2.5 g at 5...2000 Hz

Not applicable

Vibration, non-operating

5 g at 5...2000 Hz

Not applicable

Shock, operating

all modules except relay contact

30.0 g (3 pulses, 11 ms)

Not applicable

Shock, operating

relay contact modules - OW, OX, IO combo

10.0 g (3 pulses, 11 ms)

Not applicable

Shock, non-operating

50.0 g (3 pulses, 11 ms)

Not applicable

Free fall (drop test)

Portable, 2.268 kg (5 lb) or less at 0.762 m (30 in.)

(six drops)

Not applicable

Portable, 2.268 kg (5 lb) or more at 0.1016 m (4 in.) (three

flat drops)

Not applicable

Safety

Dielectric withstand: 1500V ac

UL 508, CSA C22.2 No. 142

Isolation between communication circuits: 500V dc

Not applicable

Isolation between backplane and I/Os: 1500V ac

Not applicable

Flammability and electrical ignition: UL94V-0

Not applicable

Certification

UL listed to US and Canadian Safety Standards

Class I, Groups A, B, C or D, Division 2

CE compliant for all applicable directives

C-Tick marked for all applicable acts

Not applicable