56

System Installation Recommendations

System Overview

Refer to the following sections when planning your system layout.

Environment and Enclosure

ATTENTION

This equipment is intended for use in a Pollution Degree 2

industrial environment, in overvoltage Category II applications

(as defined in IEC publication 60664-1), at altitudes up to 2000

m (6561.7 ft) without derating.
This equipment is considered Group I, Class A industrial

equipment according to IEC/CISPR Publication 11. Without

appropriate precautions, there may be potential difficulties

ensuring electromagnetic compatibility in other environments

due to conducted as well as radiated disturbance.
This equipment is supplied as open type equipment. It must be

mounted within an enclosure that is suitably designed for those

specific environmental conditions that will be present and

appropriately designed to prevent personal injury resulting from

accessibility to live parts. The interior of the enclosure must be

accessible only by the use of a tool. Subsequent sections of this

publication may contain additional information regarding

specific enclosure type ratings that are required to comply with

certain product safety certifications.
See NEMA Standards publication 250 and IEC publication

60529, as applicable, for explanations of the degrees of

protection provided by different types of enclosure. Also, see

the appropriate sections in this publication, as well as the

Allen-Bradley Industrial Automation Wiring and Grounding

Guidelines, publication 1770-4.1, for additional installation

requirements pertaining to this equipment.