Specifications

Processor General
Specifications

The table below lists general specifications for SLC 500 modular processors.

Attribute (1747-)

SLC 5/01

SLC 5/02 SLC 5/03

SLC 5/04

SLC 5/05

L511

L514

L524

L531

L532

L533

L541

L542

L543

L551

L552

L553

Program memory

(words)

1 K

4 K

4 K

8 K

16 K

32 K

16 K

32 K

64 K

16 K

32 K

64 K

I/O capacity

3940 discrete

4096 discrete

Remote I/O capacity

Not applicable

Processor memory and chassis power limit up to 4096 inputs and 4096 outputs

Chassis/slots, max

3 Chassis/30 Slots of I/O

Standard RAM

Capacitor -
2 weeks

(2)

optional lithium battery -

5 years

Lithium battery

2 years

Capacitor - 30 minutes minimum

Memory back-up

options

EEPROM

Flash EPROM

Status indicators

Run

CPU Fault

Forced I/O

Battery Low

Run

CPU Fault

Forced

I/O

Battery

Low

COMM

Run

CPU Fault

Forced I/O

Battery Low

RS-232

DH-485

Run

CPU Fault

Forced I/O

Battery Low

RS-232

DH

+

Run

CPU Fault

Forced I/O

Battery Low

RS-232

Ethernet

Power supply loading 90 mA at 5V dc

500 mA at 5V dc

1A at 5V dc

1A at 5V dc

0 mA at 24V dc

175 mA at 24V dc

0 mA at 24V dc

(4)

0 mA at 24V dc

Clock/calendar
accuracy

(1)

Not applicable

±54 sec./month at 25 °C (77 °F); ±81 sec./month at 60 °C (140 °F)

Program scan hold-up

time after loss of

power

20 ms...3 s (dependent on power supply loading)

Noise immunity

NEMA Standard ICS 2-230

Temperature rating

operating: 0 °C...60 °C (32 °F...140°F); storage: -40 °C...85 °C (-40 °F...185 °F)

Humidity

5 to 95% without condensation

Shock, operating

30 g

Vibration

Displacement:.015 in., peak-to-peak at 5...57 Hz
Acceleration: 2.5 g at 57...2000 Hz