160

Troubleshooting

Status Indicator

The following
error exists

Probable Cause

Recommended Action

PO

WE

R

RU

N

FORCE

FL

T

DH485/DH+/ENET

BA

TT

RS232

On Off Off On Off On Off NVRAM error

Major hardware

failure due to noise,

improper grounding, or

poor power source.

Cycle power and see if the error repeats itself. If the

error clears, you should be able to download the

operating system. If the error persists, contact your

Rockwell Automation representative.

On Off On On On Off On Hardware

Watchdog

Timeout

Major hardware

failure due to noise,

improper grounding, or

poor power source.

Cycle power and see if the error repeats itself. If the

error clears, you should be able to download the

operating system. If the error persists, contact your

Rockwell Automation representative.

On Off On On On Off Off Fatal Hardware

Error

Major hardware

failure due to noise,

improper grounding, or

poor power source.

Cycle power and see if the error repeats itself. If the

error clears, you should be able to download the

operating system. If the error persists, contact your

Rockwell Automation representative.

On Off Off On Off On On Corrupted

Operating

System Memory

Module

The operating system

on the Flash EPROM is

corrupt.

Cycle power and see if the error repeats itself. If the

error persists, either contact your Rockwell Automation

representative for a new operating system memory

module, or download the old operating system.

On Off On On Off On Off Flash EPROM

Failure

The processor flash is

corrupt.

Cycle power and see if the error repeats itself. If the

error clears, you should be able to download the

operating system. If the error persists, contact your

Rockwell Automation representative.

On Off On On On On Off Corrupt or

Missing

Operating

System

The operating system

is missing or has been

corrupted.

Cycle power and see if the error repeats itself. If the

error clears, you should be able to download the

operating system. If the error persists, contact your

Rockwell Automation representative for a new

operating system.

On Off On On Off On On Downloadable

Operating

System Failure

Failure during

transmission of

downloadable

operating system.

Download the operating system.

On Off Off On On On Off Incompatible

Platform

The upgrade of the

operating system is

incompatible with the

processor hardware.

Use an operating system that is compatible with your

processor hardware.

On Off Off On On On On Memory

Write-Protected

An attempt was made

to download the

operating system onto

write-protected

memory.

Change the jumper on the processor to the program

position.

Advertising