Publication 1747-UM011G-EN-P - June 2008

64

System Installation Recommendations

Special Grounding Considerations for dc Applications using
1746-P3 (previous to revision B)

This information describes special wiring considerations for the 1746-P3
power supply that is not labeled as revision (REV) B or later-.

Keep wire length as short as possible.

ATTENTION

Any voltage applied to the 1746-P3 DC NEUT terminal will be

present at the SLC logic ground and the processor DH-485 port.

To prevent unwanted potentials across the logic ground of the

controller and/or damage to the SLC chassis, the DC NEUTRAL

of the external dc power source must be either isolated from

the SLC chassis ground, or connected to earth ground.

SLC Logic Ground

SLC 500 Chassis

Processor

1746-P3

Door

A jumper wire is recommended
between the DC NEUT and Chassis
Ground of the external power source.

Earth Ground

Not Used

DH-485
Port

Earth Ground

External dc Power Source

+24 VDC

DC NEUT

Chassis
Ground

Not Used
+24V dc

DC Neut

Chassis
Ground

Safety Ground