Troubleshooting

Power status indicator

on

CPU Fault status

indicator is on

All other status

indicators are off

Status of SLC 5/02

Comm status indicator

does not matter

CPU fault

CPU memory error.

Cycle power.

Faulty memory

module.

1. Remove power and then remove the memory module from

the processor.

2. Re-install the processor and re-apply power to the power

supply. If steady CPU Fault status indicator changes to

flashing, replace the existing memory module with a

replacement module.

See chapter 6 for removing and installing memory modules.

Faulty processor or

power supply.

1. Place the processor in another chassis not in the existing

system and cycle power. If steady CPU Fault status indicator

reappears, replace the processor.

2. If CPU Fault status indicator clears, monitor the line power

going to the power supply in existing system. Replace

existing system power supply if line power checks OK.

Processor firmware

installed

incorrectly.

If upgrading the processor to a different firmware level, verify

that the firmware chip orientation matches the upgrade kit

directions.

Power status indicator

is on

CPU Fault status

indicator is flashing

All other status

indicators are off

Status of SLC 5/02

Comm status indicator

does not matter

CPU major fault

Initial CPU factory

power-up

condition.

1. See chapter 8 and follow the start-up procedures.

2. Clear processor memory to get rid of the flashing CPU Fault

status indicator.

Hardware/software

major fault

detected.

(erratic, repetitive

power cycling can

cause a processor

major hardware

fault)

1. Monitor Status File word S:6 for major error code.

2. Refer to the SLC 500 Instruction Set Reference Manual,

publication 1747-RM001, for error codes and additional

troubleshooting information.

3. Remove hardware/software condition causing fault.

4. Clear Status File S:1/13 major error bits, if set.

5. Clear Status File S:5 major error bits, if set.

6. Clear Status File S:6 major error code (optional).

7. Attempt to put processor in run mode.

If unsuccessful, repeat recommended action steps above.

SLC 5/01 and SLC 5/02 Processor Errors

If the status indicators
indicate

The following
error exists

Probable Cause

Recommended Action

Advertising