Publication 1747-UM011G-EN-P - June 2008

System Installation Recommendations 65

IMPORTANT

SLC 500 series A chassis (1746-A4, 1746-A7, 1746-A10, and

1746-A13) manufactured before November 1992 have a resistor

between the logic ground and chassis ground as the drawing on

the following page illustrates. This resistor could be damaged if

the wiring recommendation described within the attention box

above is not followed. See the figure on the following page for

the location of the resistor. SLC 500 series A chassis (1746-A4,

1746-A7, 1746-A10, and 1746-A13) with a manufacture date of

November 1992 or later do not have this resistor. SLC 500

series B chassis have a 1 MW resistor that limits the current

between logic ground and chassis ground.

SLC Chassis

1746-P3

Functional Ground

Not Used

Not Used

+24V dc

DC Neut
Chassis
Ground

Safety Ground

Controller Logic Ground

Functional Ground