Publication 1747-UM011G-EN-P - June 2008

24

Quick Start for Experienced Users

10.

(Optional) Return the SLC 5/03, SLC 5/04, or SLC 5/05 processor to initial factory conditions.

Reference

Use this procedure if the communication channels are shut down due to configuration
parameters, or if you absolutely cannot establish communication with the processor.

Chapter 10
(Troubleshooting)

1. Remove power from the SLC 500 power supply.

2. Remove the processor from the chassis.

3. Disconnect the battery by removing the battery connector from its socket.

4. Locate the VBB and GND connections on the right side of the motherboard.

5. Place a small bladed screwdriver across the VBB and GND connections and hold for 60

seconds. This returns the processor to the initial factory conditions.

ATTENTION

If you return the processor to the initial factory conditions, the communication

configurations are returned to their default settings and the user program is

cleared.