Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual

Page 195

Advertising
background image

Publication 1747-UM011G-EN-P - June 2008

Setting Up the DH-485 Network 195

Single Cable Connection

Multiple Cable Connection

Wire/Terminal Connections for DH-485 Connectors for Belden #3106A

Wire/Terminal connections for DH-485 connectors for Belden #9842.

For this wire/pair

Connect this wire

To this terminal

Shield/drain

Non-jacketed

Terminal 2 - Shield

Blue

Blue

Terminal 3 - (Common)

White/drain

White with orange stripe

Terminal 4 - (Data B)

Orange with white stripe

Terminal 5 - (Data A)

For this wire/pair

Connect this wire

To this terminal

Shield/drain

Non-jacketed

Terminal 2 - Shield

Blue/white

White with blue stripe

Cut back - no connection

(1)

(1)

To prevent confusion when installing the communication cable, cut back the white with blue stripe wire
immediately after the insulation jacket is removed. This wire is not used by DH-485.

Blue with white stripe

Terminal 3 - (Common)

White/orange

White with orange stripe

Terminal 4 - (Data B)

Orange with white stripe

Terminal 5 - (Data A)

IMPORTANT

In 1747-AIC interface series A, terminal 5 was called DATA B

and terminal 4 was called DATA A. In this case, use terminal

numbers only and ignore signal names DATA B and DATA A. The

internal circuitry of the series A is the same as series B.

6 Termination
5 A
4 B
3 Common
2 Shield
1 Chassis
Ground

Orange with White Stripes

White with Orange Stripes

Shrink Tubing
Recommended

Blue (#3106A) or Blue with
White Stripes (#9842)

Drain Wire

Belden #3106A or #9842

to Previous Device

to Successive Device