Setting Up the DH+ Network

Wiring Connectors for DH+
Communication for SLC 5/04
Processors

To connect Allen-Bradley devices with other devices over DH

+

, you must wire

the 3-pin cable connectors so that communication can occur through the
cabling. Each device requires its own node address.

Terminate the DH+ link on both ends by connecting a 150

Ω

, 1/2 W resistor

between terminals 1 and 2 of the 3-pin connector when you are
communicating at 57.6 Kbaud with a PLC-5 processor or 115.2 Kbaud with
other SLC 5/04 processors. Use an 82

Ω

, 1/2 W resistor if you are

communicating at 230.4 Kbaud with other SLC 5/04 processors or series E
enhanced PLC-5 processor.