Troubleshooting

can then use a programmer/operator interface device to change the
processor mode.

Identifying SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors

The following status indicators and tables provide you with
information regarding error messages, possible cause(s) for the error,
and recommended action to resolve the error.

ATTENTION

If you clear a processor fault using the keyswitch, the

processor immediately enters the Run mode.

SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors

If the status indicators
indicate

The following
error exists

Probable Cause

Recommended Action

All status indicators are

off

Status of any

Communication status

indicator does not

matter

Inadequate system

power

No line power.

1. Verify proper line voltage and connections on the power

terminals.

2. Verify proper 120/240V power supply jumper selection. See

page 106.

Power supply fuse

blown.

1. Check the incoming power fuse, check for proper incoming

power connections. Replace fuse.

2. If fuse blows again, replace the power supply.

See page 139 on fuse replacement.

Power supply

overload.

1. Remove line power to power supply. remove several output

modules from the chassis. wait five minutes. reapply power.

2. If condition reoccurs, re-calculate module configuration

power required and verify proper power supply selection.

See page 36. This problem can occur intermittently if power

supply is slightly overloaded when output loading and

temperature varies.

Defective power

supply.

1. Recheck other probable causes.

2. Monitor the line power to chassis power supply for possible

transient or shorting.

3. Replace the power supply.