Troubleshooting

Power status indicator is

on

DH-485, DH+, or ENET

status indicator is

flashing

FLT status indicator is off

or flashing

Status of Run, Force,

Batt, and RS232 status

indicators do not matter

The SLC 5/03 or

SLC 5/04

processor is trying

to establish

communication,

but cannot find

other active nodes.

(The DH-485 or

DH+ status

indicator is

flashing green.)

DH-485 or DH+

communication

parameters are

improperly set up.

1. Check communication parameters of programmer.

Programmer and processor communication rate must match.

Programmer and processor node addresses must be

different.

2. Try different combinations of:

a. communication rate (default is 19.2 K for DH-485 and 57.6

K for DH+)

b. node address (default is 1)

3. Try to increase the maximum node address.

(default is 31 for DH-485)

Bad connection of

communication

device.

1. Check cable continuity.

2. Check cable connections between programmer and

processor.

3. Check communication device (for example, the 1747-PIC

interface). Replace if necessary.

Low or no power to

communication

device.

1. Verify proper power supply selection and backplane loading.

(1747-PIC and 1747-AIC interface draw power off the

backplane.)

2. Verify proper 120/240V power supply jumper selection. See

page 106.

Duplicate drop is

detected. (The DH+

status indicator is

flashing red.)

Another DH+

device is already

on the DH+

network at this

node address.

1. Remove this device from the DH+ network.

2. Cycle power.

3. Reset the node address to an unused node before

reconnecting device to the DH+ network. (Can perform reset

if on-line via channel 0 RS-232 port without disconnecting

from DH+.)

An ENET fault is

being reported via

a code. (The ENET

status indicator is

flashing red.)

A hardware or

software fault has

occurred.

Contact Rockwell Automation for assistance.

SLC 5/03. SLC 4/04, and SLC 5/05 Communication Errors

If the status indicators
indicate

The following
error exists

Probable Cause

Recommended Action