Troubleshooting

Identifying SLC 5/02 Processor Communication Errors

SLC 5/02 Processor Communication Errors

If the status indicators
indicate

The following
error exists

Probable Cause

Recommended Action

Power status indicator is

on

Comm status indicator is

off

CPU Fault status

indicator is off or

flashing

Status of Run, Forced

I/O, and Battery Low

status indicators does

not matter

The SLC 5/02

processor is not

receiving data and

is not

communicating

with the

programmer

DH-485

communication

parameters are

improperly set up.

1. Check communication parameters of programmer.

Programmer and processor communication rate must match.

Programmer and processor node addresses must be

different.

2. Try different combinations of:

a. communication rate (default is 19.2 K)

b. node address (default is 1)

3. Try to increase the maximum node address.

(default is 31)

Bad connection of

communication

device.

1. Check cable continuity.

2. Check cable connections between programmer and

processor.

3. Check communication device (for example, the 1747-PIC

interface). Replace if necessary.

Low or no power to

communication

device.

1. Verify proper power supply selection and backplane loading.

(The 1747-PIC and 1747-AIC interface draw power off the

backplane.)

2. Verify proper 120/240V power supply jumper selection. See

page 106.

Power status indicator is

on

Comm status indicator is

on

CPU Fault status

indicator is off or

flashing

Status of Run, Forced

I/O, and Battery Low

status indicators does

not matter

The SLC 5/02

processor is

receiving data, but

is not

communicating

with the

programmer

DH-485

communication

parameters are set

up improperly.

1. Check communication parameters of programmer.

Programmer and processor communication rate must match.

Programmer and processor node addresses must be

different.

2. Try different combinations of:

a. communication rate (default is 19.2 K)

b. node address (default is 1)

3. Try to increase the maximum node address.

(default is 31)

Power status indicator is

on

CPU Fault status

indicator is on

Status of all other status

indicators does not

matter

A fatal error has

occurred

Excessive noise or

a faulty SLC 5/02

processor.

1. Cycle power to obtain flashing CPU Fault status indicator and

default program.

2. Examine the error code following the power cycle. Take

appropriate action.

3. Reload the program.

4. Contact your local Rockwell Automation representative if the

error persists.