Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual

Page 157

Advertising
background image

Publication 1747-UM011G-EN-P - June 2008

Troubleshooting 157

Power status indicator is

on

RS232 status indicator is

flashing

FLT status indicator is off

or flashing

Status of Run; Force;

DH-485, DH+, or ENET;

or Batt status indicators

do not matter

The processor is

trying to establish

communication,

but cannot find

other active nodes

DH-485

communication

parameters are set

up improperly.

1. Check communication parameters of programmer.

Programmer and processor communication rate must match.

Programmer and processor node addresses must be

different.

2. Try different combinations of:

a. communication rate (default is 19.2 K for DH-485)

b. node address (default is 1)

3. Try to increase the maximum node address. (default is 31 for

DH-485)

Bad connection of

communication

Device.

1. Check cable continuity.

2. Check cable connections between programmer and

processor.

3. Check communication device (for example, the 1747-PIC

interface). replace if necessary.

Low or no power to

communication

device.

1. Verify proper power supply selection and backplane loading.

(1747-PIC and 1747-AIC interface draw power off the

backplane.)

2. Verify proper 120/240V power supply jumper selection. See

page 106.

SLC 5/03. SLC 4/04, and SLC 5/05 Communication Errors

If the status indicators
indicate

The following
error exists

Probable Cause

Recommended Action