System Installation Recommendations

Typical Installation

The figure below consists of some components that make up a typical
installation.

Spacing Your Controller

The figure on the following page depicts acceptable layouts. Follow the
recommended minimum spacing to allow for convection cooling within the
enclosure. Air temperature in the enclosure must be kept within a range of
0 °C...60 °C (32 °F...140 °F).

1.

NEMA-rated enclosure suitable for
your application and environment that
shields your controller from electrical
noise and airborne contaminants.

2.

Disconnect device, to remove power
from the system

3.

Fused isolation transformer or a
constant voltage transformer, as your
application requires

4.

Master control relay/emergency-stop
circuit

5.

Terminal blocks or wiring ducts

6.

Suppression devices for limiting EMI
(electromagnetic interference)
generation

Disconnect
Device

Isolation
Transformer

SLC 500
Controller

MCR

(1)

(2)

(3)

(4)

(6)

(5)

ATTENTION

Vertical mounting is not recommended due to thermal

considerations.

IMPORTANT

Be careful of metal chips when drilling mounting holes for the

controllers. Do not drill holes above a mounted SLC 500

controller.