Publication 1747-UM011G-EN-P - June 2008

Troubleshooting 147

Power status indicator

is on

Run status indicator is

on

Forced I/O status

indicator is on

All other status

indicators are off

Status of SLC 5/02

Comm status indicator

does not matter

System does not

operate per ladder

logic

User forced I/O is

disabling operation.

1. Monitor program file on-line and identify forced I/O.

2. Disable appropriate forces and test system conditions again.

Power status indicator

is on

Run status indicator is

on

Forced I/O status

indicator is flashing

All other status

indicators are off

Status of SLC 5/02

Comm status indicator

does not matter

System does not

operate per

programmed

forces

User programmed

forces are not

enabled.

1. Monitor program file on-line and identify programmed

forces.

2. Enable appropriate forces and test system conditions again.

Once forces are enabled, the Forced I/O status indicator

turns On (steady).

Power status indicator

is on

CPU Fault status

indicator is flashing

Battery Low status

indicator is on

All other status

indicators are off

Status of SLC 5/02

Comm status indicator

does not matter

CPU major error

with low or no

battery back-up

Loss of RAM during

power-down.

1. Verify battery is connected. See page 136.

2. Replace the battery if you want RAM battery backup. See

page 136. If you want to back up RAM with the capacitor in a

SLC 5/01 (1747-L511), add or replace the Battery Low status

indicator jumper.

3. Refer to processor major fault recommended action steps.

SLC 5/01 and SLC 5/02 Processor Errors

If the status indicators
indicate

The following
error exists

Probable Cause

Recommended Action