Communicating with Devices on an Ethernet Network

Configuration Parameters

Configuration Using
RSLogix 500 Programming
Software

Refer to the documentation provided with your programming
software.

Configuration Via BOOTP

BOOTP (bootstrap protocol) is a low-level protocol that TCP/IP nodes
use to obtain start-up information. By default, the SLC 5/05 processor
broadcasts BOOTP requests at powerup. The BOOTP Valid parameter
remains clear until a BOOTP reply has been received. BOOTP lets
you dynamically assign IP Addresses to processors on the Ethernet
Link.

To use BOOTP, a BOOTP Server must exist on the local Ethernet
subnet. The server is a computer that has BOOTP Server software

Parameter

Description

Default

Status

Diagnostic File

Number

The file number of the diagnostic counter for this channel. A Diagnostic File Number value

of zero means that no diagnostics file has been configured for this channel. The Diagnostic

File Number must be an integer within the limits of 7, 9...255.

0

read/write

MSG

Connection

Timeout

The amount of time (in ms) allowed for a MSG instruction to establish a connection with the

destination node. The MSG Connection Timeout has 250 ms resolution and a range from

250...65,500.

15,000 ms

read/write

MSG Reply

Timeout

The amount of time (in ms) that the SLC 5/05 processor will wait for a reply to a command

that it has initiated via a MSG instruction. The MSG Reply Timeout has 250 ms resolution

and a range from 250...65,500.

3000 ms

read/write

Inactivity

Timeout

The amount of time (in minutes) that a MSG connection may remain inactive before it is

terminated. The Inactivity Timeout has a 1 minute resolution and a range from 1...65,500

minutes.

30 minutes

read/write

IP Address

The SLC 5/05 internet address (in network byte order). The internet address must be

specified to connect to the TCP/IP network.

0

(undefined)

read/write

Subnet Mask

The SLC 5/05 subnet mask (in network byte order). The Subnet Mask is used to interpret IP

addresses when the internet is divided into subnets. A Subnet Mask of all zeros indicates

that no subnet mask has been configured.

0

read/write

Gateway

Address

The address of a gateway (in network byte order) that provides connection to another IP

network. A Gateway Address of all zeros indicates that no gateway has been configured.

0

read/write

BOOTP Enable The BOOTP enable switch. When BOOTP is enabled, the SLC 5/05 processor attempts to

learn its network related parameters at powerup via a BOOTP request. There must be a

BOOTP server on the network capable of responding to this BOOTP request. When BOOTP is

disabled, the SLC 5/05 processor uses the locally configured network related parameters

(for example, IP Address, Subnet Mask, Broadcast Address).

1 (enabled)

read/write

Hardware

Address

The SLC 5/05 Ethernet hardware address.

Ethernet

hardware

address

read only