Identifying the Components of Your Processor 91

BATT

(Color: red)

On (steady)

The battery voltage has fallen below a

threshold level, or the battery is missing or

not connected.

Off

The battery is functional.

FORCE

(Color: amber)

Flashing

One or more input or output addresses have

been forced to an On or Off state but the

forces have not been enabled.

On (steady)

The forces have been enabled.

Off

No forces are present or enabled.

DH

+

(Color: green or

red)

On (steady)

The Communications Active bit (S:1/7) is set

in the System Status file and the processor is

actively communicating on the DH+ network.

Flashing green

The processor is trying to establish

communication, but there are no other active

nodes on the DH+ network.

Flashing red

There are duplicate nodes on the link with the

same node address.

RS-232

(Color: green)

On (steady)

DF1/Modbus RTU

Master/ASCII mode

The SLC 5/04 processor is transmitting on the

network.

Off

DF1/Modbus RTU

Master/ASCII mode

The SLC 5/04 processor is not transmitting on

the network.

On (steady)

DH-485 mode

The Communications Active bit (S:33/4) is set

in the System Status file and the processor is

actively communicating on the DH-485

network.

Flashing

DH-485 mode

The processor is trying to establish

communication, but there are no other active

nodes on the DH-485 network.

Off

DH-485 mode

A fatal error is present (no communication).

(1)

If the status indicators on the SLC 5/04 processor turn on in a predefined sequence, the SLC 5/04 processor is