82

Identifying the Components of Your Processor

SLC 5/01 Hardware Components

The table below provides a general explanation of the SLC 5/01
processor status indicators.

SLC 5/01 Status Indicators

PC RUN

CPU FAULT

FORCED I/O

BATTERY LOW

SLC 5/01 CPU

Memory
Module and
Socket

Left Side View

Front View

DH-485
Channel 1

Battery
(provides back-up
power for the
CMOS RAM)

Serial Number and Catalog Number

Processor
Status
Indicator

(1)

(1)

See chapter 10 for more information on status indicator status.

When It Is

Indicates that

PC RUN

(Color: red)

On (steady)

The processor is in the Run mode.

Off

The processor is in a mode other than Run.

CPU FAULT

(Color: red)

Flashing (at power up)

The processor has not been configured.

Flashing (during

operation)

The processor detects a major error either in

the processor, chassis or memory.

On (steady)

A fatal error is present (no communication).

Off

There are no errors.

FORCED I/O

(Color: red)

Flashing

One or more input or output addresses have

been forced to an On or Off state but the

forces have not been enabled.

On (steady)

The forces have been enabled.

Off

No forces are present or enabled.

BATTERY LOW

(Color: red)

On (steady)

The battery voltage has fallen below a

threshold level or the battery and the battery

jumper are missing.

Off

The battery is functional, or the battery

jumper is present.