Dte dce – Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual

Page 218

Advertising
background image

Publication 1747-UM011G-EN-P - June 2008

218

RS-232 Communication Interface

2760-RB Module to a Modem (Hardware Handshaking Enabled)

(1) Connect the shield of the cable to the GND pin on one end only. Leave the other end open.

2760-RB Module to a SLC 5/03, SLC 5/04, or SLC 5/05 Processor, Personal
Computer, 1770-KF3 Module, or PLC-5 Processor (Hardware Handshaking
Disabled)

(1) You can also use the 1747-CP3 cable.
(2) Jumpers are only needed if you cannot disable the hardware handshaking on the port.
(3) Connect the shield of the cable to the GND pin on one end only. Leave the other end open.

1

3

2

7

8

6

5

4

8

1

2

3

4

5

6

7

20

22

1

3

4

5

6

7

20

2

9

(1)

(1)

TXD

RXD

RTS

CTS

DSR

COM

DTR

GND

TXD

RXD

RTS

CTS

DSR

COM

DTR

DCD

GND

RI

25-Pin 2760-RB

9-Pin

25-Pin

DTE

DCE

Modem

1

3

2

7

8

6

5

4

8

2

3

4

5

6

7

20

1

3

4

5

6

7

20

2

1

(2)

(2)

(2)

(2)

(3)

(3)

TXD

RXD

RTS

CTS

DSR

COM

DTR

GND

DCD

RXD

TXD

DTR

COM

DSR

RTS

CTS

GND

25-Pin 2760-RB

9-Pin

25-Pin

DTE

DTE

Peripheral

Device