Setting Up the DH-485 Network 185

1747-UIC USB to DH-485
Interface Converter

The 1747-UIC interface lets you connect DH-485 devices directly to a
computer’s USB port. It features an RS-232 port for connection to
SLC 5/03 and later processors, MicroLogix processor, PanelView 300
and later terminals, 1761-NET-AIC+ interface, and Logix controllers, as
well as an RS-485 port for connection to SLC 5/03 and lower
processors, PanelView 300 and later terminals, and 1747-AIC interface.
The 1747-UIC interface can communicate with devices on the DH-485
network at 19.2 Kbaud.

Connecting to the RS-232 Port

USB (DF1)

RS485 (DH485)

RS232 (DH485)

USB to DH485

INTERFACE CONVERTER

USB

OK

SW

DH485

R

C

US

CAT

S

ER

FRN

1747-UIC

A

X.X

Mfg

XXXX

LISTED IND. CONT. EQ. FOR HAZ.

LOC. A196,

OPERATING TEMP CODE TAG

CLASS 1 GROUPS A, B, C, AND D, DIV. 2

MADE IN INDIA

N223

SLC 5/03, SLC 5/04, SLC 5/05

Processor (channel 0)

PanelView 300 Operator

Interface and later

Personal

Computer with

USB Port

1747-UIC
Interface

AIC+ Interface

ControlLogix Controller

CompactLogix Controller

FlexLogix Controller

MicroLogix Controller

Connect the following DH-485 equipment to
the RS-232 port

Using cable

SLC 5/03, SLC 5/04, and SLC 5/05 processor

(channel 0)

1747-CP3, 1756-CP3

1761-NET-AIC (AIC+)

Advanced Interface Converter

1747-CP3, 1756-CP3 (Port 1, 9-pin D)

1761-CBL-PM02 (Port 2, 8-pin DIN)

PanelView 300 and later operator interface with

RS-232 (DH-485) port

2711-NC13

MicroLogix controller

PanelView 300 Micro (DH-485) operator interface

1761-CBL-PM02

CompactLogix controller

1747-CP3, 1756-CP3

FlexLogix controller

1747-CP3, 1756-CP3

ControlLogix controller

1747-CP3, 1756-CP3