Publication 1747-UM011G-EN-P - June 2008

Setting Up the DH+ Network 225

Minimizing Noise

To minimize the affect of noise on the SLC 5/04 processor, ground the cable
shields to earth via 0.01

μ

F capacitors as shown in the DH+ wiring example

below. Only directly ground the shield at one point on the network.

SLC 5/04 CPU

PROC

PROG

FORCE

COMM

BATT

RUN

R
E
M

PLC±5/20
PROGRAMMABLE
CONTROLLER

1

2

1

2

A

B

SLC 5/04 CPU

1

2

RUN

PROG

FORCE

RS232

BATT

DH+

FLT

RUN

REM

RUN

PROG

FORCE

RS232

BATT

DH+

FLT

RUN

REM

Clear
Shield
Blue

Clear
Shield
Blue

Clear
Shield
Blue

Terminating
Resistor

Terminating
Resistor

Connector

Connector

Connector

Belden #9463 Cable

Belden #9463 Cable

0.01

μ

F

Shield

(1)

Shield

0.01

μ

F

Shield

Earth Ground

Earth Ground

Earth Ground

(1) To chassis ground directly at one point only in the network.