Troubleshooting

Power status indicator is

on

RS232 status indicator is

off

FLT status indicator is off

or flashing

Status of Run; Force;

DH-485, DH+, or ENET;

or Batt status indicators

do not matter

The processor is

not transmitting

Channel is

configured for

DH-485 mode.

Check communication parameters of channel configuration.

Also, refer to your programming software documentation.

RS232/DF1

parameters are set

up improperly.

Check the following communication parameters of programmer

and channel configuration.

1. communication rate - programmer and processor

communication rates must match

2. DF1 node addresses (default is 1 for half-duplex, and 9 for

full-duplex) - programmer and processor addresses must be

different

3. error checking

4. number of data bits

Hardware problem. 1. Check cable connections.

2. Check cable pinouts. Also, see appendix C for RS-232

pinouts.

Power status indicator is

on

FLT status indicator is on

Status of all other status

indicators do not matter

A fatal error has

occurred

Excessive noise or

a faulty processor.

1. Cycle power to obtain flashing FLT status indicator and

default program.

2. Examine the error code following the power cycle. Take

appropriate action.

3. Reload the program.

4. Contact your local Rockwell Automation representative if the

error persists.

SLC 5/03. SLC 4/04, and SLC 5/05 Communication Errors

If the status indicators
indicate

The following
error exists

Probable Cause

Recommended Action