Troubleshooting 155

Identifying SLC 5/03, SLC 5/04, and SLC 5/05 Processor
Communication Errors

SLC 5/03. SLC 4/04, and SLC 5/05 Communication Errors

If the status indicators
indicate

The following
error exists

Probable Cause

Recommended Action

Power status indicator is

on

DH-485, DH+, or ENET

status indicator is off

FLT status indicator is off

or flashing

Status of Run, Force,

Batt, and RS232 status

indicators do not matter

Fatal error and no

communication

Inadequate system

power.

1. Check line power.

2. Check 120/240V power supply jumper selection. See

page 106. Also, see the recommended actions for

inadequate system power on page 150.

Communication

channel is shut

down.

Check communication channel configuration with your

programming software. Also, see page 161 to return the

processor to initial factory conditions.

Communication

channel is

damaged.

Replace the processor.

Power status indicator is

on

RS232 status indicator is

off

FLT status indicator is off

or flashing

Status of Run; Force;

DH-485, DH+, or ENET;

or Batt status indicators

do not matter

Fatal error and no

communication

Inadequate system

power.

1. Check line power.

2. Check 120/240V power supply jumper selection. See

page 106. Also, see the recommended actions for

inadequate system power on page 150.

Communication

channel is shut

down.

Check communication channel configuration with your

programming software. Also, see page 161 to return the

processor to initial factory conditions.

communication

channel is

damaged.

Replace the processor.

Channel

configured for DF1

or User mode.

See your programming software documentation for channel

configuration information.