Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual

Page 20

Advertising
background image

Publication 1747-UM011G-EN-P - June 2008

20

Quick Start for Experienced Users

5.

Wire power to the power supply.

Reference

Connect incoming power.

Chapter 6
(Installing Your
Hardware
Components)

ATTENTION

Turn off incoming power before connecting wires. Failure to do so could cause

injury to personnel and/or equipment.

User Power

Incoming Power

User Power

Incoming Power

Incoming
Power

1746-P1 and 1746-P2

1746-P3

1746-P4

1746-P6

NOT USED
NOT USED
+24V dc

dc NEUT
CHASSIS GROUND

PWR OUT +24V dc
PWR OUT COM
+125V dc

dc NEUT
CHASSIS GROUND

User Power

PWR OUT +24V dc
PWR OUT COM
120/240V ac

V ac NEUT
CHASSIS GROUND

PWR OUT +24V dc
PWR OUT COM

85 to 132V ac

JUMPER
170 to 250V ac

L1: 85 to 132/170 to 250V ac

L2: NEUTRAL

CHASSIS GROUND

Incoming
Power

1746-P5

PWR OUT +24V dc
PWR OUT COM
+48V dc
dc NEUT
CHASSIS GROUND

Incoming
Power

+12/24V dc

dc NEUT
CHASSIS GROUND

Incoming
Power

User Power

User Power

NOT USED

NOT USED

1746-P7

IMPORTANT

Terminal screws on the 1746-P1, 1746-P2, 1746-P3,

1746-P5, 1746-P6, and 1746-P7 power supplies

should be tightened with a maximum torque of 1 Nm

(8.8 lb-in).
Terminal screws on the 1746-P4 power supply

should be tightened with a max torque of 0.8 Nm

(7 lb-in).