Selecting Your Hardware Components 35

SLC Communication Options

Communication
Protocol

Processor

SLC 5/01

SLC 5/02

SLC 5/03

SLC 5/04

SLC 5/05

DH-485 peer-to-peer receive only

receive and initiate

receive and initiate

DH-485 via RS232

port

receive and initiate

(9)

receive and initiate

(9)

receive and initiate

(9)

DF1 via RS232 port

(full-duplex or

half-duplex master

or slave)

receive only

(1)

receive only

(1)

receive and initiate

receive and initiate

receive and initiate

ASCII via RS232 port

receive and initiate

receive and initiate

receive and initiate

Data Highway Plus

(DH+)

receive only

(2)

receive only

(2)

receive and initiate

(5)

receive and initiate

receive and initiate

(5)

Ethernet

receive and initiate

(6)

receive and initiate

(6)

receive and initiate

DeviceNet

receive and
initiate

(3)

receive and
initiate

(3)(7)

receive and
initiate

(3)(7)

receive and
initiate

(3)(7)

ControlNet

receive and
initiate

(4)

receive and
initiate

(4)(8)

receive and
initiate

(4)(8)

receive and
initiate

(4)(8)

Modbus RTU Master

initiate only

initiate only

initiate only

(1)

A 1747-KE or 1770-KF3 interface is required to bridge from DF1 (full-duplex or half-duplex slave only) to DH485 network.

(2)

A ControlLogix gateway with a 1746-DHRIO interface and a 1756-DH485 interface is required to bridge from DH+ to DH-485 network.

(3)

A 1747-SDN module is required for scanning I/O and for explicit messaging on DeviceNet network.

(4)

A 1747-SCNR module is required for scanning I/O and for explicit messaging on ControlNet network.

(5)

The SLC 5/04’s channel-to-channel passthru feature may be used to bridge between DH+ and DH-485 network or between DH+ and DF1 full-duplex network (DH+ to DF1
full-duplex passthru available starting with OS401). Another option is to use the 1785-KE interface to bridge between DH+ and DF1 full-duplex or DH+ and DF1 half-duplex
master/slave network.

(6)

A 1761-NET-ENI interface is required to bridge from DF1 full-duplex to Ethernet network.

(7)

A 1761-NET-DNI interface is required to bridge from DF1 to DeviceNet network.

(8)

A 1747-KFC15 module or 1770-KFC15 interface is required to bridge from DF1 to ControlNet network.

(9)

If using 1747-AIC interface for isolation, connect to DH-485 network using 1747-PIC interface. If using a 1761-NET-AIC interface for isolation, connect directly to DH-485
network with 1747-CP3 serial cable (or equivalent RS-232 null-modem cable).

TIP

The 1785-KE module requires the use of a 1771 series chassis

and power supply.