Publication 1747-UM011G-EN-P - June 2008

System Installation Recommendations 69

Grounded ac Power-Distribution System with Master-Control
Relay

Power Supply Required Input Voltage Characteristics

The applied input voltage must be at or below 132V ac RMS (265V ac
RMS in 240 Volt mode).

Minimum acceptable value of the applied input voltage must be above
85V ac RMS (170V ac RMS in 240 Volt mode).

The frequency of the applied voltage must be within 47...63 Hz.

Both the positive and negative half cycles must be symmetrical and
conform to these requirements.

1

+ –

Enclosure
Wall

Connect when
applicable

Suppressor

To Motor
Starters

Back-panel
Ground Bus

Step-down
Transformer

Grounded Conductor

Equipment-
Grounding
Conductors

Start

Suppressor

MCR

MCR

FUSE

Multiple E-stop
Switches

Controller
Power Supply

Incoming
ac

1FU

Grounding-electrode
Conductor to
Grounding-electrode
System

L1

GND

N or L2

Suppressor

Input Module
Wiring Arm

Output Module
Wiring Arm

Output
Actuator

Input
Sensor

MCR

MCR

User dc
Supply

The I/O circuits form a net
inductive load switched
by the MCR contacts.
Therefore, a suppressor is
needed across the line at
the load side of the MCR
contacts.

Disc.

2FU
3FU

L1
L2
L3

L1
L2
L3