Publication 1747-UM011G-EN-P - June 2008

Troubleshooting 153

Power status indicator

is on

CPU Fault status

indicator is flashing

All other status

indicators are off

Status of any

Communication status

indicator does not

matter

CPU major fault

Initial CPU factory

power-up condition.

1. See page 121 and follow the start-up procedures.

2. Clear processor memory to get rid of the flashing CPU Fault

status indicator.

Hardware/software

major fault

detected.

(erratic, repetitive

power cycling can

cause a processor

major hardware

fault)

1. If the error occurred during the download of a new program

to the processor, check the position of the J4 jumper. See

page 159. If the jumper is not in the protected position:

a. Place the jumper in the protected position

b. Re-download a valid user program to the processor

2. Use programmer to monitor and clear the fault (or if

keyswitch in REM position):

a. Monitor Status File word S:6 for major error code.

b. Refer to your programming software documentation or the

SLC 500 Instruction Set Reference Manual, publication

1747-RM001, for error codes and additional

troubleshooting information.

c. Remove hardware/software condition causing fault.

d. Clear Status File S:1/13 major error bits, if set.

e. Clear Status File S:5 major error bits, if set.

f. Clear Status File S:6 major error code (optional).

g. Attempt to put processor in run mode.

If unsuccessful, repeat recommended action steps above.

3. Use the keyswitch to clear the fault. Toggle the keyswitch to

PROG and back to RUN. (See page 149). If fault occurs again,

use programmer to get error code and determine the source

of the problem.

SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors

If the status indicators
indicate

The following
error exists

Probable Cause

Recommended Action