System Installation Recommendations 57
Hazardous Location Considerations
Products marked CL1, DIV 2, GP A, B, C, D are suitable for use in Class I,
Division 2, Groups A, B, C, D or non-hazardous locations only. Each product
is supplied with markings on the rating nameplate indicating the hazardous
location temperature code. When combining products within a system, the
most adverse temperature code (lowest “T” number) may be used to help
determine the overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the local authority
having jurisdiction at the time of installation.
WARNING
EXPLOSION HAZARD
•
Do not disconnect equipment unless power has been
removed or the area is known to be non-hazardous.
•
Do not disconnect connections to this equipment unless
power has been removed or the area is known to be
non-hazardous. Secure any external connections that mate
to this equipment using screws, sliding latches, threaded
connectors, or other means provided with this product.
•
Substitution of components may impair suitability for Class
I, Division 2.
•
All wiring must comply with N.E.C. article 501-4(b).