88

Identifying the Components of Your Processor

FORCE

(Color: amber)

Flashing

One or more input or output addresses have been forced to an On or Off state but the

forces have not been enabled.

On (steady)

The forces have been enabled.

Off

No forces are present or enabled.

DH-485

(Color: green)

On (steady)

The Communication Active bit (S:1/7) is set in the System Status file and the processor is

actively communicating on the DH-485 network.

Flashing

The processor is trying to establish communication, but there are no other active nodes on

the DH-485 network.

Off

A fatal error is present (no communication).

RS-232

(Color: green)

On (flashing)

DF1/Modbus RTU

Master/ASCII mode

The SLC 5/03 processor is transmitting on the network.

Off

DF1/Modbus RTU

Master/ASCII mode

The SLC 5/03 processor is not transmitting on the network.

On (steady)

DH-485 mode

The Communications Active bit (S:33/4) is set in the System Status file and the processor

is actively communicating on the DH-485 network.

Flashing

DH-485 mode

The processor is trying to establish communication, but there are no other active nodes on

the DH-485 network.

Off

DH-485 mode

A fatal error is present (no communication).

(1)

If the status indicators on the SLC 5/03 processor turn on in a predefined sequence, the SLC 5/03 processor is in the process of downloading a new operating system.

(2)

See chapter 10 for more information on status indicator status.