Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual

Page 167

Advertising
background image

Publication 1747-UM011G-EN-P - June 2008

Troubleshooting 167

Off

On/energized

Your output

device will not

turn off and the

program

indicates that it

is off.

Output device is

incompatible.

Check specifications.

Output circuit off-state

leakage current may

exceed output device

specification.

Check specifications. Use load resistor to bleed off

leakage current. See output specifications.

Incorrect wiring.

Check wiring. Disconnect from SLC processor and verify

device operation.

Output device is

shorted or damaged.

Verify device operation. Replace device.

Output circuit is

damaged.

Check wiring. Try other output circuit. Replace module.

Off/de-energized Your program

indicates that the

output circuit is

on or the output

circuit will not

turn on.

Programming problem. Check for duplicate outputs and addresses using search

function.

If using subroutines, outputs are left in their last state

when not executing subroutines.

Use the force function to force output on. If this does not

force the output on, output circuit is damaged. If the output

does force on, then check again for logic/programming

problem.

Output is forced off in

program.

Check processor FORCED I/O or FORCE status indicator and

remove forces.

Output circuit is

damaged.

Use the force function to force the output on. If this forces

the output on, then there is a logic/programming problem.

If this does not force the output on, the output circuit is

damaged. Try other output circuit. Replace module.

If your
Output
Circuit
status
indicator
is

And your output
device is

And

Probable Cause

Recommended Action

Advertising