Important planning considerations, Hardware considerations – Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual

Page 189

Advertising
background image

Publication 1747-UM011G-EN-P - June 2008

Setting Up the DH-485 Network 189

Important Planning
Considerations

Carefully plan your network configuration before installing any
hardware. Listed below are some of the factors that can affect system
performance:

Amount of electrical noise, temperature, and humidity in the
network environment

Number of devices on the network

Connection and grounding quality in installation

Amount of communication traffic on the network

Type of process being controlled

Network configuration

The major hardware and software issues you need to resolve before
installing a network are discussed in the following sections.

Hardware Considerations

You need to decide the length of the communication cable, where
you will route it, and how to protect it from the environment where it
will be installed.

When the communication cable is installed, you need to know how
many devices are to be connected during installation and how many
devices will be added in the future. The following sections will help
you understand and plan the network.

Number of Devices and Length of Communication Cable

You must install a 1747-AIC link coupler for each node on the
network. If you plan to add nodes later, provide additional link
couplers during the initial installation to avoid recabling after the
network is in operation.

The maximum length of the communication cable is 1219 m (4000 ft).
This is the total cable distance from the first node to the last node on
the network.

Advertising