4 - mounting your slc 500 control system, Mounting modular hardware style units, Chapter 4 – Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual

Page 75: Mounting your slc 500 control system, Slot modular chassis, Chapter

Advertising
background image

75

Publication 1747-UM011G-EN-P - June 2008

Chapter

4

Mounting Your SLC 500 Control System

This chapter provides mounting dimensions for:

4, 7, 10, and 13-slot chassis.

link coupler (AIC).

Data Terminal Access Module (DTAM).

DTAM Plus Operator Interface.

DTAM Micro Operator Interface.

AIC+ Advanced Interface Converter.

DNI DeviceNet Network Interface.

ENI EtherNet Network Interface.

Mounting Modular
Hardware Style Units

You can mount the modular hardware style units directly to the back panel of
your enclosure using the mounting tabs and #10 or #12 screws. The torque
requirement is 3.4 Nm (30 lb-in) maximum.

4-slot Modular Chassis

(1) Dimensions for 1746-P1 power supply.

(2) Dimensions for 1746-P2, 1746-P3, 1746-P5, 1746-P6, and 1746-P7 power supplies.

(3) Dimensions for 1746-P4 power supply.

45

(1.77)

215

(8.46)

235

(9.25)

70

(2.76)

145

(5.71)

171

(6.73)

140

(5.51)

(6.22)

171

(6.73)

140

158

11 Dia.
(0.433)

(5.51)

1.0

(0.04)

5.5 Dia.

(0.217)

5.5 Dia

(0.217)

14

(0.55)

261

(10.28)

Front View

millimeters
(inches)

Left Side View

(1)

(2)

(3)

Advertising