Troubleshooting

Power status indicator

is on

Run status indicator is

on

All other status

indicators are Off

Status of any

Communication status

indicator does not

matter

System inoperable,

no major CPU

faults detected

User program logic

error.

1. Monitor logic in Run mode and verify desired I/O status.

2. Check for minor CPU faults.

Defective I/O

devices or I/O

wiring.

Test inputs and outputs according to I/O troubleshooting

procedures starting on page 163.

Power status indicator

is on

CPU Fault status

indicator is on

All other status

indicators are off

Status of any

Communication status

indicator does not

matter

CPU fault

CPU memory error.

Cycle power.

Faulty memory

module.

1. Remove power and then remove the memory module from

the processor.

2. Re-install the processor and re-apply power to the power

supply. If steady CPU Fault status indicator changes to

flashing, replace the existing memory module with a

replacement module.

Refer to 6 for removing and installing memory modules.

Faulty processor or

power supply.

1. Place the processor in another chassis not in the existing

system and cycle power. If steady CPU Fault status indicator

reappears, replace the processor.

2. If CPU Fault status indicator clears, monitor the line power

going to the power supply in existing system. Replace

existing system power supply if line power checks OK.

Processor firmware

installed

incorrectly.

If upgrading the processor to a different firmware level, verify

that the firmware chip orientation matches the upgrade kit

directions.

SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors

If the status indicators
indicate

The following
error exists

Probable Cause

Recommended Action